Managed and maintained by Unified Consulting Group.
Equipment Area:
- 100
psf floor load space
- Heavy
load freight elevators or loading dock access to the
space
- Roof
rights with satellite space available
- HVAC
- Under-floor
cooling provided by computer-room equipment
- Cooling
not less than 150 BTU/h per square foot with an N+1
redundancy
- Temperature
is maintained at 72 degrees F dry bulb at ASHRAE 1%
- In
the event of a power interruption HVAC systems (and
entire facility) operate on diesel generators
- 30%
to 60% humidity non-condensing. Humidity control delivered
through ATS/Liebert units via infra-red humidifier
Electrical Service:
- 1,000
to 1,600 amps at 480 volt total capacity, depending
on site
- 80
to 85 watts per square foot including HVAC
- 120/208
VAC and -48VDC available
- 100%
generator backup
- Generator
capacity 600-2000 KW
- Size
of fuel tank 1,000 to 2,000 gallons
- Generator
both auto start and auto transfer. Isolation bypass
feature on automatic transfer switch
- 24
hour run time fuel capacity
- Two
hour response for fuel delivery
- UPS
System
- 15
minute battery backup
- UPS
connected to backup power
- Voltage
output 480 transformed to 120/208 V
- 48
Volt DC Battery Plant
- 1200
amp expandable to 4800 amp
- 2
hour battery reserve non-redundant, 4 hours redundant
-
"True" A/B feeds
Security and Access:
- Access
to equipment area 24/7 days via card key and pass code
only
- Non-secured
personnel may enter equipment area by escort only
- Locking
cabinets and/or cages
- Full
CCTV surveillance
- Falcon
equipment monitoring system supported by INTEG-operated
NOC
Fire Suppression Systems:
- Pre-action
sprinkler rated for telecommunication equipment/computer
room
- Integrated
smoke/heat detector system
- Under-floor
leak detection system
Space Options:
- Caged
space within facility
- Open
space for racks and/or cabinets
- Separately
demised (drywall) space available
Telecommunications Services:
- Pre-run
conduit assures rapid connection to new carriers. Large
number of access providers in buildings assures the
lowest possible telecommunication link charges
- Access
providers are encouraged to locate muxes within Switch
and Data site to facilitate interconnectivity
- Overhead
cable trays are provided for connectivity